Maximo Monitor| Digital twin performanceRO-1201
3D view →-

Membrane condition: normalised flow, salt passage and pressure drop

ASTM D4516 normalisation to 25 °C and the reference net driving pressure, as % of the clean-membrane baseline at the same seawater temperature. Dashed lines: cleaning triggers (flow −10 %, salt passage +10 %, pressure drop +15 %). Last 2 hours.

Normalised permeate flow (NPF)Normalised salt passage (NSP)Normalised pressure drop (NdP)

Membrane water flux vs. net driving pressure

Average flux of the 280 SW30HRLE-440i elements (11,480 m²) against the train NDP. Solid: clean membranes at the live seawater temperature (solution-diffusion, A fitted to the DuPont test point, TCF exp(2640(1/298 − 1/T))). Dashed: 20 °C and 35 °C. Grey band: 10 % flux loss, where a clean is due. Dot: live, with trail.

Clean, live temperatureClean, 20 / 35 °CMeasured (trail)

Reverse osmosis train

Cartridge filters, HP pump in parallel with the PX energy recovery and booster, the 40-vessel rack in 4 banks, permeate and brine, with live sensor values. Red = beyond the twin's alarm limit.

Condition sensors

Bars against the alarm limits in the twin file (red line).

Twin health: expected vs. actual

Measured vs. expected